RUEN
Compressed air treatment

Refrigerated Air Dryer with R410A, 1.5–90 m³/min

PricePrice on request
Discuss by phone: 8 (800) 700-49-01

Specifications

Air flow
1.5–90 m³/min
Refrigerant
R410A
Working pressure
0.4–1.6 MPa
Dew point
+2…+10 °C
Models
17 models, FD-15 to FD-900

Description

Refrigerated compressed air dryer using R410A refrigerant. Working pressure up to 1.6 MPa, 17 sizes from 1.5 to 90 m³/min, 220 or 380 V supply.

Key features

  • R410A refrigerant;
  • working pressure 0.4–1.6 MPa;
  • pressure dew point +2…+10 °C;
  • compact models up to 11 m³/min run on 220 V single-phase.

Use in plastics production

  • air drying for screw compressor stations up to 1.5 MPa;
  • protection of pneumatics on injection, blow molding and packaging machines;
  • air preparation for laser cutting (up to 1.6 MPa).

Technical specifications

Models

ModelAir flow, m³/minPower input, kWConnectionPower supplyWeight, kgDimensions L×W×H, mm
FD-151.50.62G3/4"220 V, 1-ph58720×500×741
FD-302.80.8G1"220 V, 1-ph73720×550×741
FD-4040.97G1-1/2"220 V, 1-ph83720×600×831
FD-7071.52G1-1/2"220 V, 1-ph98720×650×921
FD-9092.1G2"220 V, 1-ph108720×680×1001
FD-110112.62G2"220 V, 1-ph124720×680×1051
FD-140142.98G2"380 V, 3-ph150780×680×1151
FD-180183.6DN65380 V, 3-ph177910×800×1251
FD-230235.2DN80380 V, 3-ph250970×850×1361
FD-280285.99DN80380 V, 3-ph2781190×900×1381
FD-340347.64DN80380 V, 3-ph3301240×950×1481
FD-3903910.59DN100380 V, 3-ph5061290×1000×1531
FD-4504511.84DN100380 V, 3-ph5441490×1050×1560
FD-5305312.82DN100380 V, 3-ph6051580×1100×1662
FD-6706715.3DN125380 V, 3-ph6611662×1250×1600
FD-8008024DN125380 V, 3-ph7801800×1300×1812
FD-9009025DN125380 V, 3-ph8001800×1300×1812

Operating conditions: inlet air temperature +5…+45 °C, pressure 0.4–1.6 MPa, ambient temperature +2…+40 °C.

How to select

Select the dryer by compressor capacity and maximum station pressure. For pressures above 1.0 MPa choose this series.

Questions and answers

Why R410A?

It is an ozone-friendly refrigerant with good thermal properties, allowing a more compact heat exchanger.

What power supply do the models use?

Up to FD-110: 220 V single-phase; from FD-140: 380 V three-phase.

Price on request. Send an enquiry and we will select the model for your air demand and pressure and prepare a quotation.

We will select equipment
for your production.

8 (800) 700-49-01
CatalogCall